Variable speed drive ATV212 - 5.5kW - 7.5hp - 480V - 3ph - EMC - IP21
-
Additional Information
Main range of product Altivar 212product or component type Variable speed drivedevice short name ATV212product destination Asynchronous motorsproduct specific application Pumps and fans in HVACassembly style With heat sinknetwork number of phases 3 phasesmotor power kW 5.5 kWmotor power hp 7.5 hp[Us] rated supply voltage 380...480 V - 15...10 %supply voltage limits 323…528 Vsupply frequency 50...60 Hz - 5...5 %EMC filter Class C2 EMC filter integratedline current 10.9 A at 380 V
8.6 A at 480 VComplementary apparent power 9.1 kVA at 380 Vprospective line Isc 22 kAcontinuous output current 12 A at 380 V
12 A at 460 Vmaximum transient current 13.2 A for 60 sspeed drive output frequency 0.5…200 Hznominal switching frequency 12 kHzswitching frequency 6...16 kHz adjustable
12...16 kHz with derating factorspeed range 1…10speed accuracy +/- 10 % of nominal slip 0.2 Tn to Tntorque accuracy +/- 15 %transient overtorque 120 % of nominal motor torque +/- 10 % for 60 sasynchronous motor control profile Voltage/frequency ratio, 2 points
Voltage/frequency ratio, 5 points
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Flux vector control without sensor, standard
Voltage/frequency ratio - Energy Saving, quadratic U/fregulation loop Adjustable PI regulatormotor slip compensation Not available in voltage/frequency ratio motor control
Automatic whatever the load
Adjustablelocal signalling 1 LED (red)DC bus energized:output voltage <= power supply voltageisolation Electrical between power and controltype of cable Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVCelectrical connection VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14
L1/R, L2/S, L3/T: terminal 6 mm² / AWG 10tightening torque 1.3 N.m, 11.5 lb.in (L1/R, L2/S, L3/T)
0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)supply Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protectionanalogue input number 2analogue input type VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm
VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bitssampling duration 2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analogresponse time FM 2 ms, tolerance +/- 0.5 ms for analog output(s)
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)accuracy +/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C
+/- 1 % (FM) for a temperature variation 60 °Clinearity error VIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input
FM: +/- 0.2 % for outputanalogue output number 1analogue output type FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits
FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bitsdiscrete output number 2discrete output type Configurable relay logic: (FLA, FLC) NO - 100000 cycles
Configurable relay logic: (FLB, FLC) NC - 100000 cycles
Configurable relay logic: (RY, RC) NO - 100000 cyclesminimum switching current 3 mA at 24 V DC for configurable relay logicmaximum switching current 5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)discrete input type F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohmdiscrete input logic Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)acceleration and deceleration ramps Automatic based on the load
Linear adjustable separately from 0.01 to 3200 sbraking to standstill By DC injectionprotection type Overheating protection: drive
Thermal power stage: drive
Short-circuit between motor phases: drive
Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overvoltages on the DC bus: drive
Break on the control circuit: drive
Against exceeding limit speed: drive
Line supply overvoltage and undervoltage: drive
Line supply undervoltage: drive
Against input phase loss: drive
Thermal protection: motor
Motor phase break: motor
With PTC probes: motordielectric strength 3535 V DC between earth and power terminals
5092 V DC between control and power terminalsinsulation resistance >= 1 mOhm 500 V DC for 1 minutefrequency resolution Display unit: 0.1 Hz
Analog input: 0.024/50 Hzcommunication port protocol METASYS N2
LonWorks
BACnet
Modbus
APOGEE FLNconnector type 1 RJ45
1 open stylephysical interface 2-wire RS 485transmission frame RTUtransmission rate 9600 bps or 19200 bpsdata format 8 bits, 1 stop, odd even or no configurable paritytype of polarization No impedancenumber of addresses 1…247communication service Read device identification (43)
Read holding registers (03) 2 words maximum
Write multiple registers (16) 2 words maximum
Write single register (06)
Monitoring inhibitable
Time out setting from 0.1 to 100 soption card Communication card for LonWorksoperating position Vertical +/- 10 degreewidth 142 mmheight 184 mmdepth 150 mmnet weight 3.35 kgpower dissipation in W 215 Wair flow 74 m3/hfunctionality Midspecific application HVACIP degree of protection IP21Variable speed drive application selection Building - HVAC Compressor for scroll
Building - HVAC Fan
Building - HVAC PumpMotor power range AC-3 4…6 kW at 380…440 V 3 phases
4…6 kW at 480…500 V 3 phasesmotor starter type Variable speed driveEnvironment electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11pollution degree 3 conforming to IEC 61800-5-1IP degree of protection IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1
IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529
IP21 conforming to EN/IEC 61800-5-1
IP21 conforming to EN/IEC 60529
IP41 on upper part conforming to EN/IEC 61800-5-1
IP41 on upper part conforming to EN/IEC 60529vibration resistance 1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27environmental characteristic Classes 3C1 conforming to IEC 60721-3-3
Classes 3S2 conforming to IEC 60721-3-3noise level 51 dB conforming to 86/188/EECoperating altitude 1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m
<= 1000 m without deratingrelative humidity 5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3ambient air temperature for operation -10…40 °C (without derating)
40…50 °C (with derating factor)ambient air temperature for storage -25…70 °Cstandards IEC 61800-3 category C3
IEC 61800-3 category C2
EN 61800-3 category C3
EN 55011 class A group 1
IEC 61800-3 environments 1 category C2
EN 61800-3 environments 1 category C3
IEC 61800-3 environments 2 category C1
EN 61800-3 environments 2 category C3
EN 61800-3 environments 2 category C1
IEC 61800-3
IEC 61800-3 environments 2 category C2
EN 61800-3 category C2
EN 61800-3 environments 1 category C2
IEC 61800-5-1
EN 61800-3 environments 1 category C1
EN 61800-3 environments 2 category C2
EN 61800-5-1
IEC 61800-3 environments 2 category C3
IEC 61800-3 environments 1 category C1
IEC 61800-3 environments 1 category C3
EN 61800-3
UL Type 1product certifications NOM 117
CSA
C-Tick
ULmarking CEPacking Units Unit Type of Package 1 PCENumber of Units in Package 1 1Package 1 Weight 3.036 kgPackage 1 Height 27 cmPackage 1 width 26 cmPackage 1 Length 26 cmUnit Type of Package 2 P06Number of Units in Package 2 12Package 2 Weight 49.43 kgPackage 2 Height 80 cmPackage 2 width 80 cmPackage 2 Length 60 cmOffer Sustainability Sustainable offer status Green Premium productEU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS DeclarationMercury free YesRoHS exemption information China RoHS Regulation Environmental Disclosure Circularity Profile WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish binsContractual warranty Warranty 18 months -
Reviews ()