ATV320U55M3C
Price upon request
-
Product is not available
Minimum Order Quantity1
Accept Small Orders No
Variable speed drive, ATV320, 5.5 kW, 200…240 V, 3 phases, compact
-
Additional Information
Complementary [Us] rated supply voltage 200...240 V - 15...10 %supply voltage limits 170…264 Vmounting mode Internal mountingrelative symmetric mains voltage tolerance 10 %maximum output voltage 240.0 Vrange of product Altivar Machine ATV320product or component type Variable speed drivenetwork frequency 50...60 Hzprospective line Isc 22 kAproduct specific application Complex machinesrelative symmetric network frequency tolerance 5 %variant Standard versioncontinuous output current 27.5 A at 4 kHz for heavy dutyEMC filter Without EMC filter4 quadrant operation possible Trueasynchronous motor control profile Voltage/frequency ratio, 5 points
Flux vector control without sensor, standard
Voltage/frequency ratio - Energy Saving, quadratic U/f
Flux vector control without sensor - Energy Saving
Voltage/frequency ratio, 2 pointssynchronous motor control profile Vector control without sensortype of cooling Fanspeed drive output frequency 0.1…599 Hznetwork number of phases 3 phasesnominal switching frequency 4 kHzsupply frequency 50...60 Hz - 5...5 %switching frequency 2...16 kHz adjustable
4...16 kHz with derating factormotor power kW 5.5 kW for heavy dutybrake chopper integrated Truecommunication port protocol Modbus serial
CANopenapplication in industrial area permitted Trueapparent power 12.4 kVA at 240 V (heavy duty)output voltage <= power supply voltageovervoltage category IIIregulation loop Adjustable PID regulatormotor slip compensation Automatic whatever the load
Adjustable 0...300 %
Not available in voltage/frequency ratio (2 or 5 points)acceleration and deceleration ramps Linear
U
S
CUS
Ramp switching
Acceleration/deceleration ramp adaptation
Acceleration/deceleration automatic stop with DC injectionbraking to standstill By DC injectionprotection type Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overheating protection: drive
Short-circuit between motor phases: drive
Thermal protection: drivefrequency resolution Display unit: 0.1 Hz
Analog input: 0.012/50 Hzmethod of access Slave CANopenwidth 150.0 mmdepth 178.0 mmnet weight 3.5 kganalogue input number 3discrete input number 7analogue output number 1sampling duration 2 ms (AI1, AI2, AI3) - analog input
2 ms (AQ1) - analog outputaccuracy +/- 0.2 % AI1, AI2, AI3 for a temperature of -10...60 °C analog input
+/- 0.5 % AI1, AI2, AI3 for a temperature of 25 °C analog input
+/- 1 % AQ1 for a temperature of 25 °C analog output
+/- 2 % AQ1 for a temperature of -10...60 °C analog outputlinearity error AI1, AI2, AI3: +/- 0.2...0.5 % of maximum value for analog input
AQ1: +/- 0.3 % for analog outputwith safety function Safe torque off (STO) Truediscrete output number 3discrete output type Configurable relay logic: (R1A, R1B, R1C) NO/NC - 100000 cycles
Configurable relay logic: (R2A, R2B) NO - 100000 cycles
Logic: (LO)with safety function Safe Stop 1 (SS1) Truerefresh time Logic input (DI1...DI6): 8 ms (+/- 0.7 ms)
Relay output (R1A, R1B, R1C): 2 ms
Relay output (R2A, R2C): 2 mswith sft fct Safe Stop 2 (SS2) Falseminimum switching current Relay output R1, R2: 5 mA at 24 V DCwith safety function Safe Operating Stop (SOS) Falsemaximum switching current Relay output R1 on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1 on resistive load, cos phi = 1: 4 A at 30 V DC
Relay output R1, R2 on inductive load, cos phi = 0.4: 2 A at 250 V AC
Relay output R1, R2 on inductive load, cos phi = 0.4: 2 A at 30 V DC
Relay output R2 on resistive load, cos phi = 1: 5 A at 250 V AC
Relay output R2 on resistive load, cos phi = 1: 5 A at 30 V DCwith safety function Safe brake management (SBC/SBT) Falsewith safety function Safely Limited Speed (SLS) Trueisolation Between power and control terminalsinsulation resistance > 1 MOhm 500 V DC for 1 minute to earthwith safety function Safe Speed Monitor (SSM) Falsewith safety function Safe Direction (SDI) Falsepower dissipation in W Fan: 242.0 W at 200 V, switching frequency 4 kHzwith safety function Safely Limited Position (SLP) Falsewith safety function Safe Position (SP) Falsevolume of cooling air 60.0 m3/hwith safety function Safe programmable logic Falseoperating position Vertical +/- 10 degreeambient air transport temperature -25…70 °Cproduct certifications CE
ATEX
NOM
GOST
EAC
RCM
KC
REACHmarking CE
ATEX
UL
CSA
EAC
RCMEnvironment electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11vibration resistance 1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm peak to peak (f= 2…13 Hz) conforming to EN/IEC 60068-2-6shock resistance 15 gn for 11 ms conforming to EN/IEC 60068-2-27relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3ambient air temperature for operation -10…50 °C without derating
50…60 °C with derating factorambient air temperature for storage -25…70 °Cenvironmental characteristic Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3
Dust pollution resistance class 3S2 conforming to EN/IEC 60721-3-3Packing Units Unit Type of Package 1 PCENumber of Units in Package 1 1Package 1 Weight 4.226 kgPackage 1 Height 19.5 cmPackage 1 width 22 cmPackage 1 Length 33 cmUnit Type of Package 2 S04Number of Units in Package 2 2Package 2 Weight 9.22 kgPackage 2 Height 30 cmPackage 2 width 40 cmPackage 2 Length 60 cmUnit Type of Package 3 P06Number of Units in Package 3 10Package 3 Weight 55.26 kgPackage 3 Height 80 cmPackage 3 width 80 cmPackage 3 Length 60 cmOffer Sustainability EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS DeclarationMercury free YesRoHS exemption information China RoHS Regulation Environmental Disclosure Circularity Profile WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins -
Reviews ()