Controller M100 - 14I/10O relay - 220VAC
-
Additional Information
Main range of product Easy Modicon M100product or component type Logic controller[Us] rated supply voltage 100...240 V ACdiscrete I/O number 24discrete input number I2...I5: 4 fast input
I0...I1: 2 high speed input
I6...I13: 8 regular inputdiscrete output number 10 relaydiscrete input voltage 24 Vdiscrete input voltage type DCdiscrete input current 7 mA for regular input
7 mA for fast input
9 mA for high speed inputdiscrete output voltage 24 V DC
220 V ACdiscrete output current 2 Adiscrete output type Relay normally openpower consumption in VA 31…43 VA at 100...240 V AC (with max I/O)Complementary supply voltage limits 85…264 Vvoltage state 1 guaranteed >= 15 V for inputvoltage state 0 guaranteed <= 5 V for inputnetwork frequency 50/60 Hzinrush current 50 Ainput impedance 3.3 kOhm for regular input
3.3 kOhm for fast input
2.81 kOhm for high speed inputresponse time 35 µs turn-on, I2...I5 terminal(s) for fast input
100 µs turn-off, I2...I5 terminal(s) for fast input
5 µs turn-on, I0...I1 terminal(s) for high speed input
5 µs turn-off, I0...I1 terminal(s) for high speed input
10 ms turn-on, Q0...Q9 terminal(s) for relay output
10 ms turn-off, Q0...Q9 terminal(s) for relay output
35 µs turn-on, I6...I13 terminal(s) for regular input
100 µs turn-off, I6...I13 terminal(s) for regular inputconfigurable filtering time 0 ms for input
3 ms for input
12 ms for inputoutput voltage limits 30 V DC
250 V ACmaximum current per output common 4 A at COM 0
4 A at COM 1
4 A at COM 2electrical durability 100000 cycles AC-12, 240 V, 480 VA, resistive
100000 cycles DC-12, 24 V, 48 W, resistiveswitching frequency 0.1 Hz with maximum load
5 Hz without maximum loadmechanical durability 20000000 cycles for relay outputminimum load 10 mA at 5 V DC for relay outputmemory capacity 512 kB internal flash with 10000 instructions for backup of programsdata storage equipment 32 GB micro SD card (optional)execution time for 1 KInstruction 0.3 ms for event and periodic taskexecution time per instruction 0.2 µs Booleanexct time for event task 60 µs response timeregulation loop Adjustable PID regulator up to 14 simultaneous loopscontrol signal type Quadrature (x1, x2, x4) at 60 kHz for fast input (HSC mode)
Pulse/direction at 60 kHz for fast input (HSC mode)
Single phase at 60 kHz for fast input (HSC mode)
CW/CCW at 60 kHz for fast input (HSC mode)counting input number 2 fast input (HSC mode) at 60 kHz 32 bitsintegrated connection type USB port with mini B USB 2.0 connector
Non isolated serial link serial 1 with terminal block connector and RS485 interface
Non isolated serial link serial 2 with terminal block connector and RS232/RS485 interfacetransmission rate 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
12 Mbit/s for USBcommunication port protocol USB port: USB - SoMachine-Network
Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Networklocal signalling 1 LED (green)PWR:
1 LED (green)RUN:
1 LED (red)module error (ERR):
1 LED (green)SD card access (SD):
1 LED (green)SL1:
1 LED per channel (green)I/O state:electrical connection fixed screw terminal blockfor inputs
fixed screw terminal blockfor outputs
fixed screw terminal block, 4 terminal(s) for connecting the serial link1
Mini B USB 2.0 connectorfor a programming terminal
fixed screw terminal block, 3 terminal(s) for connecting the 100-240 V AC power supplymaximum cable distance between devices Shielded cable: <10 m for fast input
Shielded cable: <10 m for high speed input
Unshielded cable: <150 m for output
Unshielded cable: <50 m for regular inputinsulation Between input and internal logic at 560 V AC
Between fast input and internal logic at 560 V AC
Between input groups at 560 V AC
Non-insulated between inputs
Between output and internal logic at 1780 V AC
Between output groups at 1780 V AC
Between supply and internal logic at 1780 V ACsensor power supply 24 V DCmounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 plate or panel with fixing kit conforming to IEC 60715height 90 mmdepth 70 mmwidth 130 mmnet weight 0.351 kgEnvironment IP degree of protection IP20 with protective cover in placeproduct certifications CEstandards EN/IEC 61010-2-201
EN/IEC 61131-2electromagnetic compatibility Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz...3 GHz) conforming to EN/IEC 61000-4-3
Conducted emission - test level: 79 dBμV/m QP/66 dBμV/m AV (power lines (AC)) conforming to EN/IEC 55011
Conducted emission - test level: 73 dBμV/m QP/60 dBμV/m AV (power lines (AC)) conforming to EN/IEC 55011
Radiated emission - test level: 40 dBμV/m QP class A (10 m) conforming to EN/IEC 55011
Radiated emission - test level: 47 dBμV/m QP class A (10 m) conforming to EN/IEC 55011
Magnetic field at power frequency - test level: 30 A/m conforming to EN/IEC 61000-4-8
Electrical fast transient/burst immunity test - test level: 2 kV (power lines) conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test - test level: 2 kV (relay output) conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test - test level: 1 kV (I/O) conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test - test level: 1 kV (serial link) conforming to EN/IEC 61000-4-4
1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 2 kV (power lines (AC)) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 2 kV (relay output) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 1 kV (I/O) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 1 kV (shielded cable) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 0.5 kV (power lines (DC)) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (AC)) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 1 kV (relay output) conforming to EN/IEC 61000-4-5
Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6shock resistance 15 gn for 11 ms
30 gn for 6 msimmunity to microbreaks 10 msvibration resistance 3.5 mm at 5…8.4 Hz on symmetrical rail
1 gn at 8.4…150 Hz on symmetrical rail
3.5 mm at 5…8.4 Hz on panel mounting
3 gn at 8.4…150 Hz on panel mountingrelative humidity 10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)ambient air temperature for operation 0…55 °C (horizontal installation)ambient air temperature for storage -25…70 °Cpollution degree <= 2operating altitude 0...2000 mstorage altitude 0…3000 mPacking Units Package 1 Weight 0.410 kgPackage 1 Height 7.000 cmPackage 1 width 9.000 cmPackage 1 Length 13.000 cmOffer Sustainability Sustainable offer status Green Premium productEU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS DeclarationMercury free YesRoHS exemption information China RoHS Regulation Environmental Disclosure Circularity Profile WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins -
Reviews ()
Write a Review