TM171OF22R

SKU:TM171OF22R

Price upon request
  • Product is not available

-
+

Minimum Order Quantity1

Accept Small Orders No

Modicon M171 Optimized Flush mounting 22 I/Os
  • Additional Information

    Main
    range of product
    Modicon M171/M172
     
    product or component type
    Controller
     
    product specific application
    HVAC and pumping solution
     
    variant
    Programmable
     
    Total inputs/outputs
    22
     
    discrete input number
    6
     
    discrete output number
    1 for open collector
    3 for relay outputs SPST with same common
    2 for relay outputs SPST with independent common
     
    discrete output current
    2 A for relay
     
    analogue input number
    2 configurable
    3 analog input NTC
     
    analogue output number
    3 voltage, range: 0...10 V
    2 PWM/PPM, range: 20 kHz, 12 V, 35 mA
     
    Complementary
    number of port
    1 LAN expansion bus
     
    input/output number
    5 analog output(s)
    6 digital input(s)
    5 analog input(s)
    6 digital output(s)
     
    discrete input logic
    Sink or source (positive/negative)
     
    contacts usage
    Volt-free contacts
     
    analogue input type
    voltage 0...5 V (ratiometric)
    voltage 0...10 V
    NTC temperature probe - 50...100 °C - resolution: 0.1 °C
    current 0...20 mA/4...20 mA
    voltage 0...1 V
     
    sensor power supply
    12 V DC at 85 mA
    5 V DC at 20 mA
     
    [Us] rated supply voltage
    12...24 V +/- 20 % AC/DC
    24 V +/- 20 % DC
     
    power consumption in W
    18 W at 24...48 V AC/DC
     
    realtime clock
    Built-in clock at -10…55 °C
     
    display type
    Without display
     
    overvoltage category
    II
     
    local signalling
    1 LED (red)programmable:
    1 LED (yellow)programmable:
    1 LED (green)programmable:
     
    mounting support
    DIN rail
     
    width
    140 mm
     
    height
    110 mm
     
    depth
    61.6 mm
     
    net weight
    0.385 kg
     
    Environment
    directives
    1907/2006/EC - REACH directive
    86/188/EEC - physical agents (noise) directive
    2006/95/EC - low voltage directive
    2011/65/EU - RoHS directive
     
    standards
    EN/IEC 60730
     
    product certifications
    CE
    CURus
    CSA
    EAC
     
    ambient air temperature for operation
    -10…55 °C conforming to UL 60730-1
     
    ambient air temperature for storage
    -40…85 °C
     
    relative humidity
    10…90 % non-condensing
     
    IP degree of protection
    IP20
     
    pollution degree
    2
     
    Packing Units
    Unit Type of Package 1
    PCE
     
    Number of Units in Package 1
    1
     
    Package 1 Weight
    226 g
     
    Package 1 Height
    9 cm
     
    Package 1 width
    12.5 cm
     
    Package 1 Length
    13.2 cm
     
    Unit Type of Package 2
    S02
     
    Number of Units in Package 2
    8
     
    Package 2 Weight
    2.133 kg
     
    Package 2 Height
    15 cm
     
    Package 2 width
    30 cm
     
    Package 2 Length
    40 cm
     
    Offer Sustainability
    REACh free of SVHC
    Yes
     
    EU RoHS Directive
    Pro-active compliance (Product out of EU RoHS legal scope)
    EU RoHS Declaration
     
    Mercury free
    Yes
     
    RoHS exemption information  
    China RoHS Regulation  
    WEEE
    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins